Thermocouple performance, Resistance temperature detector (rtd) input, Rtd types & ranges – West Control Solutions Pro-EC44 User Manual

Page 253: Rtd performance, Dc linear input, Dc linear types & ranges

Advertising
background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 246

Thermocouple Performance

Calibration:

Complies with BS4937, NBS125 and IEC584.

Measurement
Accuracy:

0.1% of full selected input range

1LSD (Least significant display digit).

NOTE: Reduced performance for B Thermocouple from +100 to 600°C.
NOTE: PtRh 20% vs PtRh 40% Thermocouple accuracy is 0.25% and
has reduced performance below 800°C.

Linearization
Accuracy:

Linearization better than better

0.2°C (

0.05 typical) for J, K, L, N and

T thermocouples; than better than

0.5°C for other types.

Cold Junction:

If enabled, CJC error is better than

1

C under operating conditions.

Sensor Resistance
Influence:

Thermocouple 100Ω: <0.1% of span error.
Thermocouple 1000Ω: <0.5% of span error.

Sensor Break
Protection:

Break detected within two seconds. Process Control outputs go to the
pre-set power value. High and Senor Break Alarms operate.

Resistance Temperature Detector (RTD) Input

RTD Types & Ranges

Sensor
Type

Range in

C

Range in

F

Sensor

Type

Range in

C

Range in

F

3-Wire
PT100

-199 to 800°C

-328 to 1472°F NI120

-80 to 240°C

-112 to 464°F


Note: The Scaled Input Upper Limit and Scaled Input Lower Limit parameters,
can be used to restrict range. An optional decimal place can be displayed.

RTD Performance

Measurement
Accuracy:

0.1% of full selected input range

1LSD (Least significant display digit).

Linearization
Accuracy:

Better than

0.2°C any point (

0.05°C typical).

PT100 Input complies with BS1904 and DIN43760 (0.00385

Ω/Ω/°C).

Sensor Resistance
Influence:

Pt100 50Ω/lead balanced.
Automatic Lead Compensation: <0.5% of span error.

RTD Sensor Current:

150μA ±10%.

Sensor Break
Protection:

Break detected within two seconds. Process Control outputs go to the
pre-set power value. High and Senor Break Alarms operate.

DC Linear Input

DC Linear Types & Ranges

Input
Type

Ranges

Input

Type

Ranges

mA DC

0 to 20mA

4 to 20mA

V DC

0 to 5V

1 to 5V

mV DC

0 to 50mV

10 to 50mV

0 to 10V

2 to 10V

Potentiometer

≥100Ω

Advertising