West Control Solutions Pro-EC44 User Manual

Page 159

Advertising
background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 152

Loop 1 Control Enable Access

Value

Operator Access To Control Enable/Disable

Dec

4395

20779 41558

RW

0

Off

Hex

112B

512B

A256

1

On

Loop 1 Primary Cycle Time

Cycle Time For Primary Control Outputs

Dec

4301

20685 41370

RW

0.5 to 512.0 Seconds

Hex

10CD

50CD

A19A

Loop 1 Secondary Cycle Time

Cycle Time For Secondary Control Outputs

Dec

4302

20686 41372

RW

0.5 to 512.0 Seconds

Hex

10CE

50CE

A19C

Loop 1 Control Mode

Value

Control Mode For Loop 1

Dec

4390

20774 41548

RW

0

Standard

Hex

1126

5126

A24C

1

Cascade Mode

2

Ratio Mode

Loop 1 Control Selection

Value

Control Actuator Type Selection

Dec

4307

20691 41382

RW

0

Standard (Time Proportioned or Continuous Linear
PID)

Hex

10D3

50D3

A1A6

1

VMD (3-Point Stepping For Valve Motor Drive)

Loop 1 Control type

Value

Primary Only or Primary & Secondary

Dec

4310

20694 41388

RW

0

Single (Primary Only Control)

Hex

10D6

50D6

A1AC

1

Dual Control (Primary & Secondary Control)

Loop 1 Control Action

Value

Direction Of Control Action

Dec

4311

20695 41390

RW

0

Direct Acting

Hex

10D7

50D7

A1AE

1

Reverse Acting

PID Set 1 - Primary Prop Band

PID Set 1 Primary Proportional Band For Loop 1

Dec

4312

20696 41392

RW

Primary Proportional Band for Gain Set 1.

1 display unit to 9999 units,

but limited to 10 x scaled input span. 0 = On-Off control

Hex

10D8

50D8

A1B0

PID Set 1 - Secondary Prop Band

PID Set 1 Secondary Proportional Band For Loop 1

Dec

4313

20697 41394

RW

Secondary Proportional Band for Gain Set 1.

1 display unit to 9999 units,

but limited to 10 x scaled input span. 0 = On-Off control

Hex

10D9

50D9

A1B2

PID Set 1 - Integral Time

PID Set 1 Integral Time For Loop 1

Dec

4314

20698 41396

RW

Gain Set 1 integral time constant for loop 1

0.1 to 5999 Seconds. 0 or 6000 = OFF

Hex

10DA

50DA

A1B4

PID Set 1 - Derivative Time

PID Set 1 Derivative Time For Loop 1

Dec

4315

20699 41398

RW

Gain Set 1 derivative time constant for loop 1

0.1 to 5999 Seconds. 0 or 6000 = OFF

Hex

10DB

50DB

A1B6

Loop 1 Manual Reset

PID Set 1 Manual Reset (Bias) For Loop 1

Dec

4316

20700 41400

RW

Working point from 0 to 100 for single control or

-100 to 100 for dual control (primary & secondary)

Hex

10DC

50DC

A1B8

PID Set 1 - Overlap/Deadband

PID Set 1 - Overlap or Deadband For Loop 1

Dec

4317

20701 41402

RW

PID Set 1 overlap (+ve) or deadband (-ve) between primary &

secondary prop bands. In display units - limited to 20% of the

combined band width.

Hex

10DD

50DD

A1BA

PID Set 1 - On/Off Differential

PID Set 1 - On/Off Control Differential For Loop 1

Dec

4320

20704 41408

RW

The on-off control hysteresis (deadband) for PID Set 1.

1 to 300 display units, centred about the setpoint.

Hex

10E0

50E0

A1C0