West Control Solutions Pro-EC44 User Manual

Page 122

Advertising
background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 115

31

10 to 50mV DC

32

0 to 5V DC

33

1 to 5V DC

34

0 to 10V DC

35

2 to 10V DC

36

Potentiometer

Input 1 Engineering Units

Value

Engineering Units For Display

Dec

1025

17409 34818

RW

0

= None

Hex

0401

4401

8802

1

= °C (Default for Europe)

2

= °F (Default for USA)

3

= °K

4

= Bar

5

= pH

6

= %

7

= %RH

8

= PSI

Input 1 Maximum Display Decimal
Places

Value

Maximum Number Of Decimal Places In Display

Dec

1026

17410 34820

RW

0

None (e.g. 1234)

Hex

0402

4402

8804

1

One (e.g. 123.4)

2

Two (e.g. 12.34)

3

Three (e.g. 1.234)

Input 1 Scaled Input Lower Limit

Scaling Value Low Limit

Dec

1027

17411 34822

RW

Valid between input 1 range maximum and minimum (see

Specifications section for input details)

Hex

0403

4403

8806

Input 1 Scaled Input Upper Limit

Scaling Value High Limit

Dec

1028

17412 34824

RW

Valid between input 1 range maximum and minimum (see

Specifications section for input details)

Hex

0404

4404

8808

Input 1 Process Variable Offset

Single Point Calibration PV Offset

Dec

1029

17413 34826

RW

Used for Single Point Calibration of input 1

Valid between the scaled input lower & upper limits

Hex

0405

4405

880A

Input 1 Filter Time Constant

Input 1 Process Input Filter Time

Dec

1030

17414 34828

RW

Valid between 0.0 and 512.0

Hex

0406

4406

880C

Input 1 Process Variable

Process Input 1 Value

Dec

1031

17415 34830

RO

The current input 1 process value

Hex

0407

4407

880E

Input 1 Signal /Sensor Break Flag

Value

Process Input Break Status

Dec

1032

17416 34832

RO

0

Inactive

Hex

0408

4408

8810

1

Active (break detected)

Input 1 Signal Under Range Flag

Value

Process Input Under Range Status

Dec

1033

17417 34834

RO

0

Inactive

Hex

0409

4409

8812

1

Active (under-range detected)

Input Signal Over Range Flag

Value

Process Input Over Range Status

Dec

1034

17418 34836

RO

0

Inactive

Hex

040A

440A

8814

1

Active (over-range detected)

Input 1 Cold Junction Compensation

Value

CJC Status

Dec

1035

17419 34838

RW

0

Disabled

Hex

040B

440B

8816

1

Enabled (default)

Advertising