Aux a input parameters, Loop 1 control parameters – West Control Solutions Pro-EC44 User Manual

Page 158

Advertising
background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 151

Loop 2 Target Setpoint

Actual Setpoint Value Of Selected Loop 2 Setpoint

Dec

4203

20587 41174

RO

The Loop 1 target setpoint value when ramping

Hex

106B

506B

A0D6

Operator Access To Setpoint Ramp
Rate

Value

Operator Access To Loop 2 Setpoint Ramp Rate

Dec

4204

20588 41176

RW

0

No

Hex

106C

506C

A0D8

1

Yes

Operator Access To Setpoint Edit

Value

Operator Access To Edit Loop 2 Setpoint

Dec

4206

20590 41180

RW

0

No

Hex

106E

506E

A0DC

1

Yes

Loop 2 Selected Setpoint

Value

Selected Setpoint For Loop 2

Dec

4205

20589 41178

RO

0

Main Setpoint

Hex

106D

506D

A0DA

1

Alternate setpoint

Loop 2 Actual Setpoint

Effective Setpoint Value Of Selected Loop 2 Setpoint

Dec

8269

24653 49306

RO

The effective setpoint for loop 1

(current instantaneous value of the active setpoint source)

Hex

204D

604D

C09A

Aux A Input Parameters

Parameter Name & Register Address

Integer Int +1

Float

Access

Values

& Descriptions

Auxiliary Input A Scale Minimum

Minimum Input Scaling Value

Dec

2111

18495 36990

RW

Scale value (between ±0.001 & ±10000) when input A is at

minimum value. When used for RSP, setpoint is still constrained

by setpoint limits.

Hex

083F

483F

907E

Auxiliary Input A Scale Maximum

Maximum Input Scaling Value

Dec

2112

18496 36992

RW

Scale value (between ±0.001 & ±10000) when input A is at

maximum value. When used for RSP, setpoint is still constrained

by setpoint limits.

Hex

0840

4840

9080

Auxiliary Input A Offset

Offset Applied To Scaled Aux A Value

Dec

2113

18497 36994

RW

Changes effective setpoint (for multi-zone slaves. +ve values

added -ve values subtracted. from +/-0.001 to 20000 units or

OFF

Hex

0841

4841

9082

Auxiliary Input A Value

Auxiliary Input A Measured Value

Dec

2114

18498 36996

RO

The current input A value (scaled).

Hex

0842

4842

9084

Loop 1 Control Parameters

Parameter Name & Register Address

Integer Int +1

Float

Access

Values

& Descriptions

Loop 1 Manual Control Select

Value

Auto/Manual Mode Selection

Dec

4308

20692 41384

RW

0

Automatic Mode

Hex

10D4

50D4

A1A8

1

Manual Mode

Loop 1 Control Enable Select

Value

Loop Control Enable/Disable

Dec

4309

20693 41386

RW

0

Disable

Hex

10D5

50D5

A1AA

1

Enable

Loop 1 Auto/Manual Operator Access

Value

Operator Access To Auto/Manual Control

Dec

4394

20778 41556

RW

0

Off

Hex

112A

512A

A254

1

On

Advertising
This manual is related to the following products: