background image

Technical Data SR C000 Units

Waterside Pressure Drop Data

Unit

Valve Kv

M

SR09 C000

25.0

0.69

SR12 C000

40.0

1.11

SR15 C000

40.0

1.11

SR18 C000

63.0

1.75

Includes coil, 2 or 3 port valve and pipework.

To calculate 3 port valve pressure drop:

∆P valve =

2

M

Q

where
∆P = Pressure Drop in kPa,

Q = Water Flow Rate in l/s and M =

36

Kv

Fluid 100% water.

4

SR09D030 - C000 / SR09D040 - C000

5

SR12D045 - C000 / SR09D055 - C000

6

SR15D065 - C000 / SR15D075 - C000

7

SR18D080 - C000 / SR18D095 - C000

0

20

40

60

80

100

120

140

160

180

0.00

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

Pre

ss

ure

D

ro

p (

kP

a)

Flow Rate (l/s)