Technical Data SD CL00 Units

Waterside Pressure Drop Data

Includes coil, 2 port valve and pipework.

To calculate 2 port valve pressure drop:

∆P valve =

2

M

Q

where
∆P = Pressure Drop in kPa,

Q = Water Flow Rate in l/s and M =

36

Kv

Fluid 100% water.

Kv Cooling

Kv Bypass

SD18D115-CL00

40

40

SD22D145-CL00

63

40

SD25D180-CL00

63

40

0.0

20.0

40.0

60.0

80.0

100.0

120.0

140.0

160.0

180.0

200.0

220.0

240.0

260.0

280.0

300.0

0.00

2.00

4.00

6.00

8.00

10.00

12.00

Pre

ss

ure

D

ro

p (

kP

a)

Flow Rate (l/s)

SD18D115-CL00-0

SD22D145-CL00-0

SD25D180-CL00-0

2

1 and 3

1

SD18D115 -CL00-0

2

SD22D145-CL00-0

3

SD25D180-CL00-0

SmartCool™ 6 - 200kW

Precision Air Conditioning

156