Condensate Pumps

The SmartCool condensate pump shall be either hot water (full function units when a humidifier is fitted) or cold water
type (cooling only).

Performance

The following graphs illustrate the TOTAL static (head) pressure available. The system horizontal pipe losses and
vertical lift should be factored in when calculating the condensate pump performance.

Cold Water (Cooling only units)

IMPORTANT

The discharge line from the pump
should rise no more than 6 metres
vertically and no more than 8 metres
in total length before being interrupted
with a swan neck air break and
tundish.

Condensate Drain Tray Monitoring

A float level switch shall be incorporated into the unit drain tray for indication of a high water alarm.

Hot Water (Full function units, SN,SR,SD type units)

The cold water condensate
pump has 10mm quarter turn
plastic “barbed” connection.

The hot water condensate
pump uses 10mm (3/8”) copper
tube when connecting to the
discharge stub of the pump.

2

4

6

8

10

12

0

5.0

9.0

7.0

13.0

15.0

11.0

Head (m)

Flow Rate (l/min)

0

1

2

3

4

5

6

7

8

9

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

6.0

He

ad

(m

)

Flowrate l/min

Head (m)

0

1

2

3

4

5

6

0.0

0.5

1.0

1.5

2.0

2.5

3.0

Flow Rate (l/min)

SN, SR Units

SD Units

SmartCool™ 6 - 200kW

Precision Air Conditioning

34

Introduction

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014

Advertising