Precision air conditioning smartcool™ 6 - 200kw, Technical data, Sound data – Airedale SmartCool 11-233kW User Manual

Page 81

Advertising
background image

Overall

dB(A)

Frequency (Hz) dB

Sound Measurement

63

125

250

500

1000

2000

4000

8000

SN06D010-C000

Discharge Air

70

64

66

71

69

64

58

51

27

Return Air

68

64

66

69

68

63

58

50

26

Case Breakout

70

68

71

72

69

64

58

51

30

Sound Pressure @ 3m

56

53

57

58

54

50

44

37

15

SN06D015-C000

Discharge Air

81

75

76

81

80

75

69

62

38

Return Air

79

75

76

79

79

73

68

61

37

Case Breakout

81

79

82

83

80

75

69

62

41

Sound Pressure @ 3m

66

64

67

68

65

61

54

48

26

SN09D020-C000

Discharge Air

69

68

70

74

69

60

57

51

34

Return Air

68

68

70

72

68

58

56

50

34

Case Breakout

70

72

75

76

68

60

56

52

37

Sound Pressure @ 3m

56

57

61

61

54

45

42

37

23

SN09D025-C000

Discharge Air

76

73

72

82

75

67

63

57

40

Return Air

75

73

72

80

74

65

62

56

39

Case Breakout

77

77

77

83

74

67

63

57

43

Sound Pressure @ 3m

62

62

63

69

60

52

48

43

29

SN12D030-C000

Discharge Air

69

65

72

73

67

60

57

56

37

Return Air

68

65

72

71

66

58

56

55

36

Case Breakout

70

69

78

75

67

60

57

57

40

Sound Pressure @ 3m

55

55

63

60

52

45

42

42

26

SN12D035-C000

Discharge Air

73

64

74

78

71

64

62

58

44

Return Air

72

64

73

76

70

62

61

57

43

Case Breakout

74

68

79

79

71

64

61

58

47

Sound Pressure @ 3m

59

53

64

65

56

49

47

44

32

Technical Data

Sound Data

(1) dB(A) is the overall sound level, measured on the A scale
(2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.

Precision Air Conditioning

SmartCool™ 6 - 200kW

81

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014

Te

ch

nic

al

C0

C0

C

000

SN

Advertising