Precision air conditioning smartcool™ 6 - 200kw, Technical data sr c0c0 units, Te ch nic al c0 c0 c0 c0 sr – Airedale SmartCool 11-233kW User Manual

Page 115

Advertising
background image

Technical Data SR C0C0 Units

Electrical Data

SR12D035-C0C0

(1) Values given for full function units with standard selections for heating, humidification, supply air fans.
(2) Stated motor power is based on maximum electrical power absorbed

SR12D035-C0C0-0

SR12D035-C0C0-1

SR12D035-C0C0-2

Unit Data - Full Function

(1)

Nominal Run Amps

A

19.6

19.2

35.2

Recommended Mains Fuse Size

A

25

25

50

Unit Data - Cooling Only
Nominal Run Amps

A

5.43

5.43

9.5

Recommended Mains Fuse Size

A

10

10

16

Max Mains Incoming Cable Size

mm²

16

16

35

Mains Supply

V

400V / 3PH + N / 50Hz

380V / 3PH + N / 60Hz

220V / 3PH / 60Hz

Control Circuit

VAC

24

24

24

Evaporator Fan - Motor - Per Fan
Motor Type

EC

EC

EC

Quantity x Motor Size

(2)

kW

1 x 2.9

1 x 2.9

1 x 2.9

Full Load Amps

A

4.5

4.5

7.5

OPTIONAL EXTRAS
Electric Heating
Stage of Reheat

1

1

1

Number of Elements

3

3

3

Rating

kW

7.5

6.8

7.5

Current Per Phase

A

10.9

10.3

19.7

Humidifier
Capacity

kg/hr

3

3

3

Rating

kW

2.25

2.25

2.25

Full Load Amps

A

3.3

3.5

6

First upgrade EC Motor - Per Fan
Quantity x Motor Size

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Precision Air Conditioning

SmartCool™ 6 - 200kW

115

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014

Te

ch

nic

al

C0

C0

C0

C0

SR

Advertising