Precision air conditioning smartcool™ 6 - 200kw, Technical data sd clcl units, Te ch nic al cl cl sd – Airedale SmartCool 11-233kW User Manual

Page 183

Advertising
background image

Technical Data SD CLCL Units

Electrical Data

SD25D140-CLCL

SD25D140-CLCL-0

SD25D140-CLCL-1

SD25D140-CLCL-2

Unit Data - Full Function

(1)

Nominal Run Amps

A

79.4

79.4

142.8

Recommended Mains Fuse Size

A

100

100

200

Unit Data - Cooling Only
Nominal Run Amps

A

14.3

14.3

24.5

Recommended Mains Fuse Size

A

20

20

32

Max Mains Incoming Cable Size

mm²

70

70

185

Mains Supply

V

400V / 3PH + N / 50Hz

380V / 3PH + N / 60Hz

220V / 3PH / 60Hz

Control Circuit

VAC

24

24

24

Evaporator Fan - Motor - Per Fan
Motor Type

EC

EC

EC

Quantity x Motor Size

(2) kW

3 x 2.9

3 x 2.9

3 x 2.9

Full Load Amps

A

4.5

4.5

7.5

OPTIONAL EXTRAS

Electric Heating
Stage of Reheat

3

3

3

Number of Elements

9

9

9

Rating

kW

22.5

20.3

22.5

Current Per Phase

A

32.5

30.9

59.1

Humidifier
Capacity

kg/hr

30

30

30

Rating

kW

22.5

22.5

22.5

Full Load Amps

A

32.6

34.2

59.2

(1) Values given for full function units with standard selections for heating, humidification, supply air fans.
(2) Stated motor power is based on maximum electrical power absorbed

Precision Air Conditioning

SmartCool™ 6 - 200kW

183

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014

Te

ch

nic

al

CL

CL

SD

Advertising