Smartcool™ 6 - 200kw precision air conditioning, Technical data sr c000 units, C0 te ch ni ca l c 000 sr – Airedale SmartCool 11-233kW User Manual

Page 94: Mechanical data

Advertising
background image

SR15D065-C000-0

SR15D065-C000-1

SR15D065-C000-2

Capacity
Nom Cooling (Gross)

(1) kW

70.0

70.0

70.0

Fan Power Input (Fan Gain)

(2) kW

2.12

2.12

2.12

Dimensions - W x D x H

mm

1521 x 890 x 1980

Weight - Machine / Operating

(3) kg

461 / 512

Construction

Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black Grey (RAL 7021)

Material / Colour

Frame: Anodised Aluminium Frame with Aluminium Corners, Epoxy

Baked Powder Coated Paint - Black Grey (RAL 7021)

Cooling Coil

Copper Tube / Hydrophilic Coated Aluminium Fins

Cooling / Dehum Stages

1 (Modulated) / 1

Water volume

l

51

51

51

Water flow rate

l/s

3.33

3.33

3.33

Pressure drop

kPa

46.8

46.8

46.8

Fan & Motor

Backwards Curved, Centrifugal Direct Drive

Motor Type

EC

EC

EC

Quantity x Motor Size

(4) kW

2 x 1.96

2 x 1.96

2 x 1.96

Speed @25Pa ESP / Maximum ESP

rpm

1276 / 1560

1276 / 1560

1276 / 1560

Maximum ESP

Pa

354

354

354

Nominal Airflow

m³/s

3.80

3.80

3.80

Connections
Water Inlet / Outlet -

mm

42

42

42

Condensate Drain Hose

mm

22

22

22

Filtration

Disposable to BS EN 779-G4

Quantity

15

15

15

Electric Heating (Total)

kW

15.0

13.5

15.0

Humidifier
Capacity

kg/hr

15

15

15

Drain pump flow rate

l/m

7

7

7

Feed / Drain

3/4” BSPF Braided Flexible Hose / 19mm Hose Connection

Hot Water Condensate Pump
Head

m

5

5

5

Flow

l/m

10.8

10.8

10.8

Drain

10mm Stainless Steel Stub Connection

Cold Water Condensate Pump
Head

m

4

4

4

Flow

l/m

1.7

1.7

1.7

Drain

10mm Quarter Turn Plastic ‘Barb’ Connection

Upgraded Fan Motor - EC Motor

Backwards Curved, Centrifugal Direct Drive

Quantity x Motor Size

(4) kW

2 x 3.6

2 x 3.6

2 x 3.6

Speed @ 25Pa / Maximum ESP

rpm

1632 / 2260

1632 / 2260

1701 / 2260

Maximum ESP

Pa

903

903

854

SR15D065-C000

Technical Data SR C000 Units

Mechanical Data

(1) Entering air 24°C /45% RH water 7°C/ 12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, these values may change with different ESP.
(3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power.