Technical Data SD CLCL Units

Waterside Pressure Drop Data

Includes coil, 2 port valve and pipework.

To calculate 3 port valve pressure drop:

∆P valve =

2

M

Q

where ∆P = Pressure Drop in kPa,

Q = Water Flow Rate in l/s and M =

36

Kv

Fluid 100% water.

Kv Cooling

Kv Bypass

SD31D190-CLCL

63

63

SD35D225-CLCL

63

63

4

SD31D190 - CLCL-0

5

SD35D225 - CLCL-0

0.00

50.00

100.00

150.00

200.00

250.00

0.00

2.00

4.00

6.00

8.00

10.00

12.00

14.00

Pre

ss

ure

D

ro

p (

kP

a)

Flow Rate (l/s)

SD31D190-CLCL-0

SD35D225-CLCL-0

5

4

Precision Air Conditioning

SmartCool™ 6 - 200kW

189

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014