Precision air conditioning smartcool™ 6 - 200kw, Technical data sd cl00 units, Te ch nic al sd c l0 0 – Airedale SmartCool 11-233kW User Manual

Page 159

Advertising
background image

Technical Data SD CL00 Units

Interconnecting Wiring

*For 220V/3PH NO neutral units the Neutral connection is replaced with a live phase.

N1

Neutral (Supply 1)

301

L1 (Supply 1)

302

L2 (Supply 1)

303

L3 (Supply 1)

N2

Neutral (Supply 2)

304

L1 (Supply 2)

305

L2 (Supply 2)

306

L3 (Supply 2)

PE

Protective Earth

502

Fire Detector

583

Fire Detector

583

Smoke Detector

584

Smoke Detector

502

Remote On/Off

522

Remote On/Off

2

Condensate Pump Supply (230V)

N (3*)

Condensate Pump Supply (230V)

534

Condensate Pump High Level Alarm

535

Condensate Pump High Level Alarm

609

Flood Detection Tape / Probe

610

Flood Detection Tape / Probe

810

Supply Air Temperature Sensor

811

Supply Air Temperature Sensor

560

Non-Critical Alarm N/O

561

Non-Critical Alarm Common

563

Critical Alarm N/O

564

Critical Alarm Common

565

Critical Alarm N/C

881

BMS Connection

882

BMS Connection

883

BMS Connection

Precision Air Conditioning

SmartCool™ 6 - 200kW

159

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014