Smartcool™ 6 - 200kw precision air conditioning – Airedale SmartCool 11-233kW User Manual

Page 8

Advertising
background image

System Configurations

SN, SR Range

SD Range

The SN and SR range is designed for the following
nominal conditions:

SN C000 Units

Fans located within unit

Separate floorstand (min 350mm)

Return air of 24°C 45% RH

Water temperatures of 7°C / 12°C

SR C000 / C0C0 Units

Fans located within unit

Separate floorstand (min 350mm)

Return air of 24°C 45% RH

Water temperatures of 7°C / 12°C

The SD range is designed for the following nominal
conditions:

SD CL00 / CLCL Units

Fans located within floorstand

Floorstand integril to unit (min 600mm)

Return air of 35°C 24% RH

Water temnperatures of 18°C / 24°C

SD CH00 / CHCH Units

Fans located within floorstand

Floorstand integril to unit (min 600mm)

Return air of 24°C 45% RH

Water temperatures 7°C / 12°C

SmartCool™ 6 - 200kW

Precision Air Conditioning

8

Introduction

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014