Technical Data SD CHCH Units

Waterside Pressure Drop Data

Includes coil, 2 port valve and pipework.

To calculate 2 port valve pressure drop:

∆P valve =

2

M

Q

where

∆P = Pressure Drop in kPa,

Q = Water Flow Rate in l/s and M =

36

Kv

Fluid 100% water.

Kv Cooling

Kv Bypass

SD18D110-CH00

40

40

SD22D140-CH00

63

40

SD25D175-CH00

63

40

0.0

20.0

40.0

60.0

80.0

100.0

120.0

140.0

0.00

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

9.00

Pre

ss

ure

D

ro

p (

kP

a)

Flow Rate (l/s)

SD18D085-CHCH-0

SD22D105-CHCH-0

SD25D135-CHCH-0

1

2

3

1

SD18D085-CHCH-0

2

SD22D105-CHCH-0

3

SD25D135-CHCH-0