Smartcool™ 6 - 200kw precision air conditioning, Technical data sr c0c0 units, C0 te ch ni ca l c0 c0 sr – Airedale SmartCool 11-233kW User Manual

Page 124

Advertising
background image

Technical Data SR C0C0 Units

Waterside Pressure Drop Data

Valve Kv

M

SR09 C0C0

16.0

0.44

SR12 C0C0

25.0

0.69

SR15 C0C0

25.0

0.69

SR18 C0C0

40.0

1.11

Includes coil, 2 or 3 port valve and pipework.

To calculate 3 port valve pressure drop:

∆P valve =

2

M

Q

where ∆P = Pressure Drop in kPa,

Q = Water Flow Rate in l/s and M =

36

Kv

Fluid 100% water.

8

SR09D020 - C0C0 / SR09D025 - C0C0

9

SR12D030 - C0C0 / SR12D035 - C0C0

10

SR15D040 - C0C0 / SR15D045 - C0C0

11

SR18D050 - C0C0 / SR 18D060 - C0C0

0.0

10.0

20.0

30.0

40.0

50.0

60.0

70.0

80.0

90.0

0.00

1.00

2.00

3.00

4.00

5.00

6.00

Pre

ss

ure

D

ro

p (

kP

a)

Flow Rate (l/s)

8

9

10

11

SmartCool™ 6 - 200kW

Precision Air Conditioning

124

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014