Smartcool™ 6 - 200kw precision air conditioning, Technical data sr c0c0 units, C0 te ch ni ca l c0 c0 sr – Airedale SmartCool 11-233kW User Manual

Page 114: Mechanical data

Advertising
background image

SR12D035-C0C0

Technical Data SR C0C0 Units

Mechanical Data

SR12D035-C0C0-0

SR12D035-C0C0-1

SR12D035-C0C0-2

Capacity
Nom Cooling (Gross)

(1) kW

43.1

43.1

43.1

Fan Power Input (Fan Gain)

(2) kW

2.36

2.36

2.36

Dimensions - W x D x H

mm

1242 x 890 x 1980

Weight - Machine / Operating

(3) kg

380 / 424

Construction

Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black Grey (RAL 7021)

Material / Colour

Frame: Anodised Aluminium Frame with Aluminium Corners, Epoxy

Baked Powder Coated Paint - Black Grey (RAL 7021)

Cooling Coil

Copper Tube / Hydrophilic Coated Aluminium Fins

Cooling / Dehum Stages

1 (Modulated) / 1

Water volume

l

22

22

22

Water flow rate

l/s

2.05

2.05

2.05

Pressure drop

kPa

29

29

29.0

Fan & Motor

Backwards Curved, Centrifugal Direct Drive

Motor Type

EC

EC

EC

Quantity x Motor Size

(4) kW

1 x 2.9

1 x 2.9

1 x 2.9

Speed @25Pa ESP / Maximum ESP

rpm

1595 / 1660

1595 / 1660

1595 / 1660

Maximum ESP

Pa

124

124

124

Nominal Airflow

m³/s

3.30

3.30

3.30

Connections
Water Inlet / Outlet -

mm

42

42

42

Condensate Drain Hose

mm

22

22

22

Filtration

Disposable to BS EN 779-G4

Quantity

12

12

12

Electric Heating (Total)

kW

7.5

6.8

7.5

Humidifier
Capacity

kg/hr

3

3

3

Drain pump flow rate

l/m

7

7

7

Feed / Drain

3/4” BSPF Braided Flexible Hose / 19mm Hose Connection

Hot Water Condensate Pump
Head

m

5

5

5

Flow

l/m

10.8

10.8

10.8

Drain

10mm Stainless Steel Stub Connection

Cold Water Condensate Pump
Head

m

4

4

4

Flow

l/m

1.7

1.7

1.7

Drain

10mm Quarter Turn Plastic ‘Barb’ Connection

Upgraded Fan Motor - EC Motor
Quantity x Motor Size

(4) kW

N/A

N/A

N/A

Speed @ 25Pa / Maximum ESP

rpm

N/A

N/A

N/A

Maximum ESP

Pa

N/A

N/A

N/A

(1) Entering air 24°C /45% RH water 7°C/ 12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, these values may change with different ESP.
(3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power.