Technical Data SD CL00 Units

Performance Data SD CL00

Chilled water inlet and outlet temperatures

Air On

5 / 10 °C

7 / 12 °C

8 / 14 °C

10 / 16 °C

Temp. (°C)

TC

SC

TC

SC

TC

SC

TC

SC

/ %RH

(kW)

(kW)

(kW)

(kW)

(kW)

(kW)

(kW)

(kW)

22 / 50

124.1

96.5

97.5

84.2

74.8

72.3

59.3

59.3

SD18D115-CL00-0

24 / 45

139.2

109.3

112.7

97.2

89.7

83.7

73.4

73.4

26 / 40

152.1

122.1

125.8

110.1

103.0

96.4

86.9

86.9

22 / 50

152.0

115.9

120.9

101.3

97.2

90.4

73.0

73.0

SD22D145-CL00-0

24 / 45

169.8

130.9

138.7

116.5

115.7

106.1

89.4

89.4

26 / 40

184.9

145.9

154.1

131.6

131.5

121.5

105.2

105.2

22 / 50

199.1

151.8

158.7

132.8

128.6

118.8

96.2

96.2

SD25D180-CL00-0

24 / 45

222.1

171.4

181.8

152.7

152.4

139.2

117.5

117.5

26 / 40

241.9

191.1

201.7

172.5

172.9

159.4

137.9

137.9

22 / 50

256.3

196.6

203.8

171.9

164.0

153.5

123.8

123.8

SD31D235-CL00-0

24 / 45

286.3

222.1

233.9

197.7

195.1

180.0

151.4

151.4

26 / 40

312.1

247.7

259.8

223.5

221.7

206.3

177.9

177.9

22 / 50

297.7

227.0

237.7

198.7

193.2

177.9

144.1

144.1

SD35D270-CL00-0

24 / 45

332.2

256.4

272.1

228.3

228.7

208.3

175.7

175.7

26 / 40

361.6

285.6

301.7

257.8

259.0

238.4

206.1

206.1