Technical Data SD CHCH Units

Electrical Data

SD18D085-CHCH

SD18D085-CHCH-0

SD18D085-CHCH-1

SD18D085-CHCH-2

Unit Data - Full Function

(1)

Nominal Run Amps

A

40.3

39.7

72.2

Recommended Mains Fuse Size

A

50

50

100

Unit Data - Cooling Only
Nominal Run Amps

A

9.9

9.9

17.0

Recommended Mains Fuse Size

A

16

16

20

Max Mains Incoming Cable Size

mm²

35

35

70

Mains Supply

V

400V / 3PH + N / 50Hz

380V / 3PH + N / 60Hz

220V / 3PH / 60Hz

Control Circuit

VAC

24

24

24

Evaporator Fan - Motor - Per Fan
Motor Type

EC

EC

EC

Quantity x Motor Size

(2) kW

2 x 2.9

2 x 2.9

2 x 2.9

Full Load Amps

A

4.5

4.5

7.5

OPTIONAL EXTRAS

Electric Heating
Stage of Reheat

2

2

2

Number of Elements

6

6

6

Rating

kW

15.0

13.5

15.0

Current Per Phase

A

21.7

20.6

39.4

Humidifier
Capacity

kg/hr

8

8

8

Rating

kW

6.0

6.0

6.0

Full Load Amps

A

8.7

9.2

15.8

(1) Values given for full function units with standard selections for heating, humidification, supply air fans.
(2) Stated motor power is based on maximum electrical power absorbed

Precision Air Conditioning

SmartCool™ 6 - 200kW

163

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014