Smartcool™ 6 - 200kw precision air conditioning, Technical data sd ch00 units, Te ch ni ca l ch 00 sd – Airedale SmartCool 11-233kW User Manual

Page 140

Advertising
background image

Technical Data SD CH00 Units

Waterside Pressure Drop Data

Includes coil, 2 port valve and pipework.

To calculate 3 port valve pressure drop:

∆P valve =

2

M

Q

where ∆P = Pressure Drop in kPa,

Q = Water Flow Rate in l/s and M =

36

Kv

Fluid 100% water.

Kv Cooling

Kv Bypass

SD18D110-CH00

40

40

SD22D140-CH00

63

40

SD25D175-CH00

63

40

1

SD18D110 - CH00 - 0

2

SD22D140 - CH00 - 0

3

SD25D175 - CH00 - 0

0.0

20.0

40.0

60.0

80.0

100.0

120.0

140.0

160.0

180.0

200.0

0.00

2.00

4.00

6.00

8.00

10.00

12.00

Pre

ss

ure

D

ro

p (

kP

a)

Flow Rate (l/s)

SD18D110-CH00-0

SD22D140-CH00-0

SD25D175-CH00-0

1 and 2

3

SmartCool™ 6 - 200kW

Precision Air Conditioning

140

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014