Precision air conditioning smartcool™ 6 - 200kw, Technical data sn c000 units, Electrical data – Airedale SmartCool 11-233kW User Manual

Page 79

Advertising
background image

SN12D035-C000

SN12D035-C000-0

SN12D035-C000-1

SN12D035-C000-2

Unit Data - Full Function

(1)

Nominal Run Amps

A

22.3

22.4

39.5

Recommended Mains Fuse Size

A

32

32

50

Unit Data - Cooling Only
Nominal Run Amps

A

4.9

4.9

7.9

Recommended Mains Fuse Size

A

10

10

10

Max Mains Incoming Cable Size

mm²

16

16

35

Mains Supply

V

400V / 3PH + N / 50Hz

380V / 3PH + N / 60Hz

220V / 3PH / 60Hz

Control Circuit

VAC

24

24

24

Evaporator Fan - Motor - Per Fan
Motor Type

EC

EC

EC

Quantity x Motor Size

(2)

kW

1 x 2.4

1 x 2.4

1 x 1.95

Full Load Amps

A

3.9

3.9

5.9

OPTIONAL EXTRAS
Electric Heating
Stage of Reheat

2

2

2

Number of Elements

6

6

6

Rating

kW

6.0

5.4

6.0

Current Per Phase

A

8.7

8.3

15.8

Humidifier
Capacity

kg/hr

8

8

8

Rating

kW

6

6

6

Full Load Amps

A

8.7

9.2

15.8

First upgrade EC Motor - Per Fan
Quantity x Motor Size

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Technical Data SN C000 Units

Electrical Data

(1) Values given for full function units with standard selections for heating, humidification, supply air fans.
(2) Stated motor power is based on maximum electrical power absorbed

Precision Air Conditioning

SmartCool™ 6 - 200kW

79

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014

Te

ch

nic

al

C0

C0

C

000

SN

Advertising