Smartcool™ 6 - 200kw precision air conditioning, Ins ta lla tio n, Positioning – Airedale SmartCool 11-233kW User Manual

Page 54

Advertising
background image

Positioning

A

B

C - Floorstand

(3)

SD18D

mm

1800

880

Min 600– Max 750

SD22D

mm

2200

880

SD25D

mm

2500

880

SD31D

mm

3100

880

SD35D

mm

3500

880

Minimum Ceiling Clearance- (D)

Forward Only

Forward and 1 Side

Forward and 2 Sides

All Faces

SD18D

mm

720

500

380

250

SD22D

mm

720

500

380

250

SD25D

mm

720

500

380

250

SD31D

mm

740

550

440

280

SD35D

mm

750

590

480

300

(1) Shown with standard open floor stand.
(2) Shaded area indicates minimum service and maintenance requirements. The unit must be installed with allowance for carpet tile clearance.
(3) Dimension C denotes recommended minimum/maximum floor stand height, refer to Airedale for special applications, please specify at order.

Minimum Unit Clearance SD

Open and Enclosed Floorstand Option

SmartCool™ 6 - 200kW

Precision Air Conditioning

54

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014