Precision air conditioning smartcool™ 6 - 200kw, Technical data sd ch00 units, Te ch nic al ch 00 sd – Airedale SmartCool 11-233kW User Manual

Page 139

Advertising
background image

Technical Data SD CH00 Units

Electrical Data

SD35D255-CH00

SD35D255-CH00-0

SD35D255-CH00-1

SD35D255-CH00-2

Unit Data - Full Function

(1)

Nominal Run Amps

A

94.7

94.1

170.0

Recommended Mains Fuse Size

A

125

125

200

Unit Data - Cooling Only
Nominal Run Amps

A

18.7

18.7

32.0

Recommended Mains Fuse Size

A

25

25

40

Max Mains Incoming Cable Size

mm²

70

70

185

Mains Supply

V

400V / 3PH + N / 50Hz

380V / 3PH + N / 60Hz

220V / 3PH / 60Hz

Control Circuit

VAC

24

24

24

Evaporator Fan - Motor - Per Fan
Motor Type

EC

EC

EC

Quantity x Motor Size

(2) kW

4 x 2.9

4 x 2.9

4 x 2.9

Full Load Amps

A

4.5

4.5

7.5

OPTIONAL EXTRAS

Electric Heating
Stage of Reheat

4

4

4

Number of Elements

12

12

12

Rating

kW

30.0

27.1

30.0

Current Per Phase

A

43.4

41.2

78.8

Humidifier
Capacity

kg/hr

30

30

30

Rating

kW

22.5

22.5

22.5

Full Load Amps

A

32.6

34.2

59.2

(1) Values given for full function units with standard selections for heating, humidification, supply air fans.
(2) Stated motor power is based on maximum electrical power absorbed

Precision Air Conditioning

SmartCool™ 6 - 200kW

139

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014

Te

ch

nic

al

CH
00

SD

Advertising