Smartcool™ 6 - 200kw precision air conditioning, Technical data sd clcl units, Te ch ni ca l cl cl sd – Airedale SmartCool 11-233kW User Manual

Page 176: Performance data sd clcl

Advertising
background image

Technical Data SD CLCL Units

Performance Data SD CLCL

Chilled water inlet and outlet temperatures

Air On

5 / 10 °C

7 / 12 °C

8 / 14 °C

10 / 16 °C

Temp. (°C)

TC

SC

TC

SC

TC

SC

TC

SC

/ %RH

(kW)

(kW)

(kW)

(kW)

(kW)

(kW)

(kW)

(kW)

22 / 50

94.3

79.6

69.8

67.5

58.6

58.6

46.6

46.6

SD18D090-CLCL-0

24 / 45

106.8

90.7

82.0

77.7

70.4

70.4

58.9

58.9

26 / 40

117.7

101.9

93.0

89.2

81.9

81.9

70.6

70.6

22 / 50

125.6

101.9

96.9

89.1

76.8

76.8

62.0

62.0

SD22D120-CLCL-0

24 / 45

141.4

115.7

112.7

103.0

91.4

91.4

77.0

77.0

26 / 40

155.0

129.6

126.1

117.0

105.6

105.6

91.4

91.4

22 / 50

147.6

124.3

109.4

105.1

91.6

91.6

73.1

73.1

SD25D140-CLCL-0

24 / 45

175.0

151.2

128.4

121.0

110.0

110.0

92.2

92.2

26 / 40

184.1

159.1

145.4

138.9

127.9

127.9

110.4

110.4

22 / 50

205.3

167.7

158.0

146.6

126.0

126.0

101.8

101.8

SD31D190-CLCL-0

24 / 45

231.2

190.5

183.8

169.7

150.0

150.0

126.4

126.4

26 / 40

253.3

213.4

205.9

192.8

173.3

173.3

150.2

150.2

22 / 50

242.8

195.7

188.4

171.3

148.2

148.2

120.3

120.3

SD35D225-CLCL-0

24 / 45

272.6

222.1

218.3

197.8

175.8

175.8

148.6

148.6

26 / 40

298.2

248.5

243.9

224.5

202.8

202.8

175.9

175.9

SmartCool™ 6 - 200kW

Precision Air Conditioning

176

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014

Te

ch

ni

ca

l

CL

CL

SD

Advertising