Technical Data SR C000 Units

Interconnecting Wiring

Conn 15

Conn 16

Conn 17

Conn 14

Conn 14

N1

Neutral (Supply 1)

301

L1 (Supply 1)

302

L2 (Supply 1)

303

L3 (Supply 1)

N2

Neutral (Supply 2)

304

L1 (Supply 2)

305

L2 (Supply 2)

306

L3 (Supply 2)

PE

Protective Earth

502

Fire Detector

583

Fire Detector

583

Smoke Detector

584

Smoke Detector

502

Remote On/Off

522

Remote On/Off

2

Condensate Pump Supply (230V)

N (3*)

Condensate Pump Supply (230V)

534

Condensate Pump High Level Alarm

535

Condensate Pump High Level Alarm

609

Flood Detection Tape / Probe

610

Flood Detection Tape / Probe

810

Supply Air Temperature Sensor

811

Supply Air Temperature Sensor

560

Non-Critical Alarm N/O

561

Non-Critical Alarm Common

563

Critical Alarm N/O

564

Critical Alarm Common

565

Critical Alarm N/C

881

BMS Connection

882

BMS Connection

883

BMS Connection

*For 220V/3PH NO neutral units the Neutral connection is replaced with a live phase.

CONN14

PIN 1

7

6

4

5

3

2

1

WIRE

PIN No.

502

522

560

561

563

564

565

CONN15

PIN 1

PIN No.

WIRE

1

2

3

881

882

883

CONN16

PIN 1

PIN No.

WIRE

1

2

3

5

4

6

7

8

2

534

535

609

610

810

811

or

N

3

CONN17

PIN 1

502

PIN No.

WIRE

1

2

3

4

2

3

N or

583 or 584

SmartCool™ 6 - 200kW

Precision Air Conditioning

104

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014