Name and Location
Fill in the name and location of your Commander. These names will appear in all logs, emails and
records.

Global Settings: Temperature
Use the drop down menu to select Fahrenheit or
Celsius temperature scale.

Warning-Alarm Delay
Commander probes sample environmental
conditions once every 10 seconds and verify
conditions after 3 samples or 30 seconds.

This

delay is programmable and determines the
duration a condition must be valid prior to
taking any action

Alarm Alerts: To sense an alarm or warning condition a probe is polled three times to avoid any
potential for false alarms. As each poll is 10 seconds the total time to confirm if a condition is
valid is 30 seconds. To further avoid false alarms the Master Admin can program a Warning-
Alarm delay which will require the condition be valid for the total programmed time prior to
taking any action.

Global Settings: Sensor Status
This setting is used to display sensor status when
communication occurs between the sensors and
Commander. It is a notification only and its
operation will not affect warning or alarm
reporting. Use the drop menu to select On or
OFF.

Email Address
This email address will receive the following
information:


1. IP address that occur when Commander is operated in the DHCP mode. When the client

receives a notification IP Address has changed, this new IP Address must be entered in the
client web browser.

2. When an existing Sensor has been unplugged or a new Sensor inserted when Commander is

ON.

3. When Commander senses an internal voltage or temperature warning or alarm condition.

You can enter more than one Email address. Multiple email addresses are separated by a space.