Dynaflow, User manual - introduction – Ransburg DynaFlow User Manual User Manual

Page 16

Advertising
background image

LN-9400-00.9

DynaFlow

TM

User Manual - Introduction

12

General:

Each Channel Module is responsible

for processing channel specific dis-

crete I/O and performing all of the

necessary PID closed loop control

functions. Data and control I/O other

than discrete is communicated

through Ransburg CAN Bus located

on the Motherboard.

Dimensions:

3U (130.5mm) H x 7H (35.2mm) W

standard 19" rack module

24 Digital Inputs

(2 Channels):

24 VDC at 2.3 ma typical per input

(optically isolated, source by default,

sink selectable)

Trigger (level): Automatic mode only - For

manual mode, fluid starts with fluid

flow on master channel.

Halt (edge): Stops current JOB # (no effect on

next JOB # in queue)

Clean (edge): Forces regulator full on for

cleaning

Run (edge): Gets next JOB # - used in conjunc-

tion with JOB # and Toggle select

bits

Gun Mask (edge): Used in conjunction with

JOB # select bits

Total Reset (edge): Resets all totals

Total Hold (level): Holds present total value

regardless of fluid flow

Transparent/PID (level): When active directs

the external analog input directly to

the transducer output

Analog Hold (level):

Freezes PID and holds cur-

rent analog control output

Load (edge): Loads fluid with controlled mix ratio

for GUNs operating in MANUAL

Mode

External Fault/

Enable (level): Enable signal input. Must

be active for fluid to be delivered by

GUN regardless of the operating

mode.

Spare:

Not used presently

Channel Module Hardware

Specifications

Channel Module Hardware

Specifications (Cont.)

12 Digital Outputs

(2 Channels):

24 VDC sourced at 300 ma max-

imum per output (Solid state relay

contacts)

Ready:

Everything is ready for operation,

configured correctly and I/O logic

OK

Active:

CHANNEL is active and controlling

Fault:

Fault has occurred

Pot Life Timer: Pot life timer expired

Clean/Load/Calibrate: Indicates Clean, Load, or

Calibrate mode is active

MVR Enable: Used to control trigger valve for

CHANNEL in fast trigger applica-

tions with Analog Hold enabled

4 Analog Inputs

(2 Channels):

Jumper selectable 0-10 VDC (de-

fault) or 4-20 ma, op-amp buffered,

10-bit A/D.

Set Point Control #1: Used for external analog

control. When used, offset and full

scale need to be set. This is

accomplished through the

MAXIMUM FLOW RATE and

MINI-

MUM FLOW RATE JOB

parameters.

Set Point Control #2: Used for external analog

10-bit A/D control. When used, off-

set and full scale need to be set.

This is accomplished through the

MAXIMUM FLOW RATE and

MINIMUM FLOW RATE JOB

parameters.

Spare #1: Not used presently

Spare #2: Not used presently

4 Analog Outputs

(2 Channels):

Jumper selectable 0-10 VDC (de-

fault) or 4-20 ma, op-amp buffered,

12-bit D/A.

Transducer Control #1: Output to proportional

E/P 12-bit D/A controller

Transducer Control #2: Output to proportional

E/P controller

Flow Rate #1: Flow Rate (scaled between MINI-

MUM FLOW RATE and MAXI-

MUM FLOW RATE

JOB param-

eters)

Flow Rate #2: Flow Rate (scaled between MINI

MUM FLOW RATE and MAXIMUM