LN-9400-00.9

DynaFlow

TM

User Manual - Installation

22

GUN INPUTS (Continued)

Description

Total Hold

Transparent/

PID

Analog Hold

Load

External Fault/

Enable

Spare Digital

Input

Analog Set

Point

Spare Analog

Input

This signal will stop all totals for the CHANNEL as long as the signal is supplied, even if the

GUN is running and there is fluid flow. The non-resettable total will not be effected. This is

most often used during flush or soft air push cycles. It can also be used to account for only

that material which is delivered onto parts.

For GUNs configured as single-component, automatic mode only. This input is only acknowl-

edged for run and load modes. This input must be supplied before the clean input or the trig-

ger input if in run mode. This signal will place the CHANNEL in single-component, open loop

mode and redirect the Analog Set Point Input directly to the E/P transducer control output.

MAXIMUM FLOW RATE, MINIMUM FLOW RATE, MVR HIGH and MVR LOW parameters

have no effect while in the transparent mode. The Out of Tolerance, FLOW TOO LOW and

FLOW TOO HIGH faults will also be disabled while in the Transparent condition.

This signal applies only to GUNs configured for single-component automatic mode. This

signal will suspend PID control and freeze the analog control output to the E/P transducer to

the current value. Normal PID operation will resume when this signal is removed. This would

typically be used during flushing operations or for control stability in situations where there

are extremely quick trigger cycles or equipment limitations. The Out of Tolerance, Flow Too

Low and Flow Too High faults will also be disabled while in the Analog Hold condition.

Load requires a pulsed signal of at least 0.25 seconds duration. The LOAD input places a

manual, two-component GUN into LOAD MODE. LOAD MODE is a special way to meter

both resin and catalyst to the applicator after the system has been through a CLEAN opera-

tion while assuring accurate ratios. A GUN can be placed into the LOAD MODE directly from

the RUN MODE. For details, refer to LOAD MODE in the "Operation" section of this manual.

External Fault will detect a low signal of at least 0.25 seconds duration. This signal must be

maintained high for normal operation.

No fluid flow will occur regardless of the operat-

ing mode if the Enable input is not active. This input is supplied as an interlock for other

equipment to automatically shut down the fluid flow controller. The system must be reset after

the External Fault is returned to the high state. Reference "Recovering From Faults" in the

"Operation" section of this manual. A Global Gun Enable system input will override this input.

Not used presently.

This is a 0-10 VDC or 4-20 ma input signal (hardware selectable on the Channel Card) which

can be used to command flow rate when the applicator is in AUTOMATIC mode. The scaling

for input signal vs. flow rate is determined by the GUN JOB # parameters, MAXIMUM FLOW

RATE and MINIMUM FLOW RATE. An Analog Set Point signal less than 0.25 VDC will cause

the controller to use the SET POINT parameter located in the JOB table instead.

Not used presently.