If a CVT or UPS is to be used on the

input to the Control Panel, use a CVT with

a Volt-Amp (VA) output rating equal to

or greater than the output voltage multi-

plied by the control panel fuse rating (see

specification section). Also make sure that

the device input ratings correspond with

the voltage and frequency of the source

supplied by the FUSED DISCONNECT.

The device output should be rated for 240

VAC maximum.

C A U T I O N

!

Before applying power to the control

panel, verify that it is set to match the

source voltage. There may sometimes be

a voltage selection switch (usually located

on the DC power supplies) to select be-

tween 120 VAC and 240 VAC or different

indicator bulbs may be required.

C A U T I O N

!

DynaFlow

TM

User Manual - Installation

19

Do not install or service this equip-

ment or perform installation or adjustment

procedures unless you are properly trained

and qualified.

Installing and servicing this equipment

requires access to parts which could cause

electric shock or serious injury if work is not

performed properly.

All work must comply with applicable local

and national regulations and codes.

W A R N I N G

!

INPUT POWER

Input supply voltage connections should be made

from a

FUSED DISCONNECT that is located in

an accessible area near the Control Enclosure.

Electrical conduit is recommended for the input

power wiring. Use 3 cond. 14 ga. wire for incom-

ing AC power supply.

If using SO type portable cord, a strain relief rated

for the diameter of cord being used is required for

protection against cord abrasion and damage.

The protective ground conductor must be termi-

nated directly to the protective conductor ground

terminal located inside the Control Enclosure which

is marked with symbol -

If there are large AC line voltage fluctuations or

voltage transients such as those typically produced

by heavy electric machinery or welding equipment,

then a constant voltage transformer (CVT) or an

uninterruptedly power supply (UPS) should be

used between the FUSED DISCONNECT and

the Control Panel.