User Manual - Maintenance

Jumper

Description

Comments

Selects 24 VDC source control or grounded

sink control for digital inputs 12-15.

2-3 = 24 VDC source

1-2 = grounded sink

Selects 24 VDC source control or grounded

sink control for digital inputs 20-23.

2-3 = 24 VDC source

1-2 = grounded sink

Selects 24 VDC source control or grounded

sink control for digital inputs 16-19.

2-3 = 24 VDC source

1-2 = grounded sink

Selects 0-10 VDC or 4-20 ma operation for

the analog control output #2.

2-3 = 0-10 VDC

1-2 = 4-20 mA

Selects 0-10 VDC or 4-20 ma operation for

the analog output #2.

2-3 = 0-10 VDC

1-2 = 4-20 mA

Selects 0-10 VDC or 4-20 ma operation for

the analog set point input #2.

2-3 = 0-10 VDC

1-2 = 4-20 mA

Selects 0-10 VDC or 4-20 ma operation for

the spare analog input #2.

2-3 = 0-10 VDC

1-2 = 4-20 mA

Inputs effected:

Trigger #2

Gun Mask #2

Transparent/PID #2

Total Hold #1

Inputs effected:

Load Mode #2

Analog Hold #2

External Fault #2

MVR Enable #2

Inputs effected:

Run #2

Halt #2

Total Reset #2

Clean #2

To the E/P transducer #2

Actual flow rate for

CHANNEL #2, scaled by

Maximum and Minimum Flow

Rate parameters

Scaled by Maximum and

Minimum Flow Rate

parameters

CHANNEL MODULE P/N: 77206-XX (Obsolete)

DAUGHTER BOARD JUMPER SETTINGS (CHANNEL 2 I/O)

Default Setting

Source

Source

Source

0-10 VDC

0-10 VDC

0-10 VDC

0-10 VDC

2-3

2-3

2-3

2-3

2-3

2-3

2-3

E3

E1

E2

E6

E7

E5

E4