DynaFlow

TM

User Manual - Operation

60

16. Trigger the GUN. If the flow rate does not

oscillate, or the oscillations decrease in amplitude

in a few seconds, increase Kd by 30 and repeat

from step 15. If the flow rate oscillates with increas-

ing amplitude, decrease Kd by 15 and repeat from

step 15. If the flow rate oscillates with a constant

amplitude, proceed to step 17.

17. Set Kd to one-eighth the present value.

18. Cycle the GUN from READY to RUN so the

new parameters are sent to the Channel Module(s).

19. At this point, the tuning procedure is com-

pleted. The resulting Kp, Ki, and Kd parameters

should produce the fastest response with minimal

over-shoot and/or oscillation. If oscillation does

occur with these PID parameters,consider re-

ducing each value by the same percentage. This

will lower the overall gain resulting in a slightly

longer time to achieve the desired set point and

a slow- er response to disturbances, such as paint

pumps.

20. For two-component GUNs, repeat steps 4

through 19 for the Slave CHANNEL.

PID Tuning Methods - Alternate PID

1. Set the maximum set point for the GUN.

2. Set Ki and Kd

parameters to zero. Do this for

both CHANNELS if this is a two-component GUN.

3. Set Kp for the Master CHANNEL based on the

following formula:

(8.0 - MVR LOW) * 25,500

Kp =

10

(Max. Gun Set Point * Ratio)

(Ratio + 1)

For example:

Max. Gun Set Point = 400 cc/min.

MVR LOW = 15 PSIG

Ratio = 3:1

(8.0 - 15) * 25,500

Kp = 10

(400 * 3)

( 4 )

= 6.5 * 25,500

300

= 552.5

= 550

4. Set Kp for the Slave CHANNEL based on the

following formula:

(8.0 - MVR LOW) * 25,500

Kp = 10

(Max. Gun Set Point)

(Ratio +1)

For example:

Max. Gun Set Point = 400 cc/min.

MVR LOW = 15 PSIG

Ratio = 3:1

(8.0 - 15) * 25,500

Kp = 10

(400)

( 4 )

= 6.5 * 25,500

100

= 1657.5

= 1660

5. Cycle the GUN from READY to RUN so the new

parameters are sent to the Channel Module(s).

6. Trigger the GUN. If the flow rates do not achieve

their individual CHANNEL set points, adjust the

upstream fluid pressures until they both are on

target.

NOTE: This may require repeated triggers and

fault resetting. Once the proper fluid pressures

are set, the maximum set point for the gun will be

flowing, ratioed properly between the CHANNELS,

with the MVR pressures at 80 PSIG.