Troubleshooting

8-3

MOD Status Indicator

Status

Cause

Corrective Action

Off

The adapter is not powered or
not properly connected to the
drive.

• Securely connect the adapter to the drive

using the Internal Interface (ribbon) cable.

• Apply power to the drive (or adapter if

mounted in a DSI External Comms Kit).

Flashing
Red

The adapter has failed the
firmware test.

• Cycle power to the drive (or adapter if

mounted in a DSI External Comms Kit).

• If cycling power does not correct the

problem, the adapter parameter settings
may have been corrupted. Reset defaults
and reconfigure the adapter.

• If resetting defaults does not correct the

problem, flash the adapter with the latest
firmware release.

Solid
Red

The adapter has failed the
hardware test.

• Cycle power to the drive (or adapter if

mounted in a DSI External Comms Kit).

• Replace the adapter.

Flashing
Green

The adapter is operational, but
is not transferring I/O data.

• Place the scanner in RUN mode.
• Program the controller to recognize and

transmit I/O to the adapter.

• Configure the adapter for the program in

the controller.

Solid
Green

The adapter is operational and
transferring I/O data.

No action required.