Configuring the Adapter

3-3

If the Node Address Switches on the adapter are set to a node address of
“00,” the value of Parameter 02 - [CN Addr Cfg] determines the
ControlNet node address.

1. Set the value of Parameter 02 - [CN Addr Cfg] to a unique node

address.

Figure 3.1 Node Address Screen on PowerFlex 4-Class HIM (22-HIM-*)

2. Reset the adapter (see

Resetting the Adapter on Page 3-6

).

The I/O configuration determines the number of drives that will be
represented on the network as one node by the adapter. If the Operating
Mode Jumper (J7 in

Figure 2.1

)

is set to the “1x” (Single mode) default

position, only one drive is represented by the adapter and Parameter 12
- [DSI I/O Cfg]
has no effect. If the Operating Mode Jumper is set to the
“5x” (Multi-Drive) position, up to five drives can be represented as one
node by the adapter.

1. Set the value in Parameter 12 - [DSI I/O Cfg].

Figure 3.2 I/O Configuration Screen on Powerflex 4-Class HIM (22-HIM-*)

When the adapter is internally mounted in a PowerFlex 40 or 400
drive, this drive is always Drive 0. Drives 1 through 4 are PowerFlex

Setting the Node Address

Default = 2

CN Addr Cfg

Parameter:

#

002

2

VALUE

LIMITS

SEL

!

Setting the I/O Configuration

Value Description

Mode Jumper Position

Single Multi-Drive

0

Drive 0 (Default)

1

Drives 0-1

2

Drives 0-2

3

Drives 0-3

4

Drives 0-4

DSI I/O Cfg

Parameter:

#

012

Drive 0

0

VALUE

LIMITS

SEL

!