Formatting a message to write to a parameter – Rockwell Automation 22-COMM-C ControlNet Adapter User Manual

Page 67

Advertising
background image

Using Explicit Messaging

6-7

Formatting a Message to Write to a Parameter

This write message example is for parameter P039 - [Accel Time 1] for a
PowerFlex 4-Class drive.

For supported classes, instances, and attributes, refer to

Appendix C

,

ControlNet Objects

.

Configuration Box

Example Value Description

Communication

Command

Service Code
Class Number
Instance Number

Attribute Number
PLC-5 Data Table

Address

Size in Elements
Port Number
Local ControlNet Node

CIP Generic

10 (Hex.)
f (Hex.)
27 (Hex.)

1 (Hex.)
N7:3

1
2
2

CIP messages are used to access the Parameter object in

the 22-COMM-C.

The code for the Set_Attribute_Single service.
The Class ID for the CIP Parameter object.
The instance number is the same as the parameter number

in Single mode operation.

The attribute number for the Parameter Value attribute.
The user-defined address for any request service data sent

by the controller.

The number of elements in the request data.
The channel on the PLC-5 used for the ControlNet network.
The node address of the 22-COMM-C adapter.