Installing the Adapter

PowerFlex 400 Frames D, E, and F

1. Remove power from the drive.

2. Use static control precautions.

3. Remove the drive cover.

4. With the adapter board right side up, remove its mounting screw

from the lower left hole. Save the screw for mounting in Step 7.

5. Connect the Internal Interface cable to the DSI port on the drive (see

Figure 2.5

).

6. With the adapter board oriented bottom side up, route the Internal

Interface cable under the adapter, and then to the mating DSI
connector on the adapter.

7. Install the adapter, bottom side up, to the right side of the display

board by snapping it into place. Then insert the adapter mounting
screw into the lower left hole on the board.

Important: Tighten the mounting screw in the adapter’s lower left

hole to ground the adapter to the drive.

Figure 2.5 Mounting and Connecting the Adapter – PowerFlex 400 Frame D, E,

and F Drives

PowerFlex 400

(Frame D shown

with cover removed)

LEDs

Internal Interface
Ribbon Cable

Adapter Installation

(Side View)

Bottom of

Adapter Board

Connector