Controllogix example, Formatting a message to read a parameter, Controllogix example -3 – Rockwell Automation 22-COMM-C ControlNet Adapter User Manual

Page 63

Advertising
background image

Using Explicit Messaging

6-3

Formatting a Message to Read a Parameter

A Get Attribute Single message is used to read a single parameter. This
example read message is for parameter d003 - [Output Current] for a
PowerFlex 4-Class drive.

Figure 6.2 Get Attribute Single Message Configuration Screens

ControlLogix Example

TIP: To display the Message Configuration screen in RSLogix 5000,
add a message instruction (MSG), create a new tag for the message
(Properties: Base tag type, MESSAGE data type, controller scope), and
click the

button in the message instruction.

Configuration Tab

Example Value

Description

Message Type

Service Type

(1)

Service Code

(1)

Class
Instance

Attribute
Destination

CIP Generic

Get Attribute Single
e (Hex.)
f (Hex.)
3 (Dec.)

1 (Hex.)
Output_Current

CIP messages are used to access the Parameter object

in the 22-COMM-C.

This service is used to read a parameter value.
The code for the requested service.
The Class ID for the CIP Parameter object.
The instance number is the same as the parameter

number in Single mode operation.

The attribute number for the Parameter Value attribute.
The tag where the data that is read is stored.

Communication Tab Example Value

Description

Path

(2)

PowerFlex_40…

The path is the route that the message will follow.

(1)

The default setting for Service Type is “Custom,” enabling entry of a Service Code not available from the Service
Type pull-down menu. When selecting a Service Type other than “Custom” from the pull-down menu, an
appropriate Hex. value is automatically assigned to the Service Code box which grays out (unavailable).

(2)

Click Browse to find the path, or type in the name of the device listed in the I/O Configuration folder.