8-7

The adapter maintains an event queue that reports the history of its
actions. You can view the event queue using a PowerFlex 4-Class HIM,
DriveExplorer (version 3.01 or higher), or DriveExecutive (version 3.01
or higher).

Figure 8.2 DriveExplorer Event View/Clear Screen

Events

Many events in the event queue occur under normal operation. If you
encounter unexpected communications problems, the events may help
you or Allen-Bradley personnel troubleshoot the problem. The following
events may appear in the event queue:

Viewing and Clearing Events

Code Event

Description

Adapter Events

0

No Event

Text displayed in an empty event queue entry.

1

Normal Startup

Power is applied to the adapter.

2

Manual Reset

The adapter was reset from the “Reset Module” parameter.

3

Watchdog T/O Flt

The software watchdog detected a failure and reset the
adapter.

4

App Updated

The application firmware has been flash updated.

5

Boot Updated

The boot firmware has been flash updated.

6

EEPROM Sum Flt

The EEPROM checksum/CRC is incorrect. The functionality
of the adapter will be limited. Default parameter values must
be loaded to clear the condition.

7 – 9

Reserved

DSI Events

10

Slave Detected

The adapter detected that the slave has been connected.

11

Slave Removed

The adapter detected that the slave has been disconnected.

12

Slave Logon

The adapter has established communications with the slave.

13

Slave Timeout

The adapter has lost communications with the slave.

14

Slave Brand Flt

The slave brand is different than the adapter.