Example configuration settings, Adapter settings, Drive settings – Rockwell Automation 22-COMM-C ControlNet Adapter User Manual

Page 76: Example configuration settings -8

Advertising
background image

7-8

Using Multi-Drive Mode

Adapter Settings

• The adapter Operating Mode Jumper (J7 in

Figure 2.1

) is set to the

“5x” (Multi-Drive) position.

• The 22-COMM-C adapter parameters are set as follows:

Drive Settings

Parameters for the five drives are set as follows:

Example Configuration Settings

Parameter

Value

Description

12 - [DSI I/O Cfg]

4

“Drives 0-4” (5 drives on 1 node)

14 - [Drv 0 Addr]

(1)

(1)

The settings for these parameters must match the parameter A104 - [Comm Node
Addr] settings in the respective drives.

1

Address of Drive 0

15 - [Drv 1 Addr]

(1)

2

Address of Drive 1

16 - [Drv 2 Addr]

(1)

3

Address of Drive 2

17 - [Drv 3 Addr]

(1)

4

Address of Drive 3

18 - [Drv 4 Addr]

(1)

5

Address of Drive 4

Parameter

Value

Drive 0 Drive 1 Drive 2 Drive 3 Drive 4

P36 - [Start Source]

5

5

5

5

5

P38 - [Speed Reference]

5

5

5

5

5

A103 - [Comm Data Rate]

(1)

(1)

The drive must be reset for a change to this parameter to take effect.

4

4

4

4

4

A104 - [Comm Node Addr]

(1)(2)

(2)

The settings for these parameters must match the respective parameter settings in the
adapter (Parameter 14 - [Drv 0 Addr] through Parameter 18 - [Drv 4 Addr]).

1

2

3

4

5

A105 - [Comm Loss Action]

0

0

0

0

0

A106 - [Comm Loss Time]

5

5

5

5

5

A107 - [Comm Format]

(1)

0

0

0

0

0