Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual

Page 102

Advertising
background image

Publication 0160-5.18 - June 2003

B-20

DeviceNet Information

Class Code 0xB3 —
160 Parameter Table Object
(Continued)

Attribute ID

Access

Rule

Parameter Name

Data

Type

Units

Description

60

Get/Set

[Zero Offset]

INT

Numeric Value

Add or subtracts an offset to the analog input.

60

Get/Set

[DN Preset Cmd]

USINT

Numeric Value

Network preset command.

61

Get/Set

[Preset Freq 0]

UINT

0.1 Hz

Sets command frequency when selected.

62

Get/Set

[Preset Freq1]

UINT

0.1 Hz

Sets command frequency when selected.

63

Get/Set

[Preset Freq 2]

UINT

0.1 Hz

Sets command frequency when selected.

64

Get/Set

[Preset Freq 3]

UINT

0.1 Hz

Sets command frequency when selected.

65

Get/Set

[Preset Freq 4]

UINT

0.1 Hz

Sets command frequency when selected.

66

Get/Set

[Preset Freq 5]

UINT

0.1 Hz

Sets command frequency when selected.

67

Get/Set

[Preset Freq 6]

UINT

0.1 Hz

Sets command frequency when selected.

68

Get/Set

[Preset Freq 7]

UINT

0.1 Hz

Sets command frequency when selected.

69

Get/Set

[Accel Time 2]

UINT

0.1 Seconds

Sets acceleration rate for presets 4 to 7.

70

Get/Set

[Decel Time 2]

UINT

0.1 Seconds

Sets deceleration rate for presets 4 to 7.

71

Get/Set

[IR Compensation]

USINT

1%

Adds a voltage to the output based on the torque current.

72

Get/Set

[Slip Comp]

USINT

0.1 Hz

Compensates for the inherent slip of the motor.

73

Get/Set

[Reverse Disable]

BOOL

Numeric Value

Setting to 1 disables the reverse.

74

Get/Set

[Analog Select]

BOOL

Numeric Value

Selects between unipolar and bipolar analog input.

75

Get/Set

[Analog Minimum]

INT

0.1%

Sets the percent of the analog input used to represent
P32 - [Minimum Freq].

76

Get/Set

[Analog Maximum]

INT

0.1%

Sets the percent of the analog input used to represent
P33 - [Maximum Freq].

78

Get/Set

[Compensation]

BOOL

Numeric Value

Setting to 1 enables the compensation.

79

Get/Set

[Current Trip]

USINT

1%

Percent above P43 - [Current Limit] at which the drive trips
immediately.

80

Get/Set

[Stall Disable]

USINT

Numeric Value

Time drive is in stall condition before causing a stall fault.

81

Get/Set

[Proc Kp Gain]

UINT

Numeric Value

Proportional gain used by the PI regulator.

82

Get/Set

[Proc Ki Gain]

UINT

Numeric Value

Integral gain used by the PI regulator.

83

Get/Set

[Proc Reference]

UINT

Numeric Value

Set point value to which PI control will regulate.

84

Get/Set

[Proc Invert]

USINT

Numeric Value

The PI control will ignore errors less than this value.

This parameter applies only to the Analog Signal Follower model.

This parameter applies only to the Preset Speed model.

Advertising