Class code 0x05 — connection object (continued) – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual

Page 90

Advertising
background image

Publication 0160-5.18 - June 2003

B-8

DeviceNet Information

Class Code 0x05 —
Connection Object (Continued)

Instance 4 Attributes: Change of State/Cyclic Instance

Common Services

Attribute ID

Access Rule

Name

Data Type

Value

1 Get

State

USINT

0 = Nonexistant
1 = Configuring
3 = Established
4 = Timed out

2

Get

Instance Type

USINT

1 = I/O Message

3

Get

Transport Class Trigger

USINT

0x82

4 Get

Produced

Connection

ID

UINT

10xxxxxx100

where xxxxxx = Node address

5

Get

Consumed Connection ID

UINT

10xxxxxx101

where xxxxxx = Node address

6

Get

Initial Comm Characteristics

USINT

0x21

7

Get

Produced Connection Size

UINT

0 to 8

8

Get

Consumed Connection Size

UINT

0 to 4

9

Get/Set

Expected Packet Rate

UINT

timer resolution of 10 msec.

12 Get/Set

Watchdog

Action

USINT

0 = transition to timed out
1 = auto delete
2 = auto reset

13

Get

Produced Connection Path Length

UINT

3

14 Get/Set

Produced

Connection

Path

[63hex][hex string]

where [hex string] is the input assembly
number in hex

15

Get

Consumed Connection Path Length

UINT

3

16

Get/Set

Consumed Connection Path

[63hex][hex string]

where [hex string] is the output
assembly number in hex

17

Get/Set

Production Inhibit Time

UINT

0

Service

Code

Implemented for:

Service

Name

Class

Instance

0x05

No

Yes

Reset

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single