Setting the baud rate, Cable lengths and baud rates, Setting the baud rate -7 – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual

Page 23: Cable lengths and baud rates -7

Advertising
background image

Publication 0160-5.18 - June 2003

Installation and Wiring

3-7

Setting the Baud Rate

Dip switches 7 and 8 set the baud rate at which the Communication
Module communicates on the network. The factory default setting for
baud rate is 125 kbps.

Figure 3.7
Setting the Baud Rate

To set the DeviceNet Baud Rate:

1. Refer to

Table 3.B

for the switch setting of a specific Baud Rate.

2. Slide switches 7 and 8 to the appropriate positions using a pointed

tool.

Important: When switches 7 and 8 are ON, the DeviceNet Baud
Rate is set to the value in parameter P104 - [NV Baud Rate].

Cable Lengths and Baud Rates

The baud rate determines the maximum length of the DeviceNet
cable. Refer to

Table 3.C

to determine cable lengths and baud rates.

1

2

3

4

5

6

7

8

O

N

ON = 1
OFF = 0

Use DIP Switch 8 and 7 for
setting the DeviceNet Baud
Rate.

Table 3.B Switch Settings for DeviceNet Module Baud Rate

Baud Rate

Switch Setting

8

Switch Setting

7

125 kbps

0

0

250 kbps

0

1

500 kbps

1

0

Set by module parameter P104

1

1

Table 3.C Baud Rate vs. Cable Length

Baud Rate

Maximum Cable Length

(Trunk Line)

125 kbps

500 meters (1640 feet)

250 kbps

250 meters (820 feet)

500 kbps

100 meters (328 feet)

Advertising