Drive program parameters (continued) – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual

Page 37

Advertising
background image

Publication 0160-5.18 - June 2003

DeviceNet Parameter Descriptions

5-9

Drive Program Parameters
(Continued)

Parameter

Number

Parameter Name

Object Mapping

(Class-Instance-

Attribute)

Description

Units

54

[Clear Fault]

0xB3-1-54

Setting to 1 performs a fault reset.

Numeric Value

55

[Probe Address]

0xB3-1-55

Used by Allen-Bradley service personnel.

Numeric Value

56

[Reset Functions]

0xB3-1-56

Sets all parameters to their factory default.

Numeric Value

57

[Program Lock]

0xB3-1-57

Locks all program group parameters.

Numeric Value

58

[Internal Freq]

0xB3-1-58

Digital frequency setpoint.

0.1 Hz

59

[Freq Select]

0xB3-1-59

Selects source of Frequency command.

Numeric Value

60

[Zero Offset]

0xB3-1-60

Add or subtracts an offset to the analog input.

Numeric Value

60

[DN Preset Cmd]

0xB3-1-92

Network preset command.

Numeric Value

61

[Preset Freq 0]

0xB3-1-61

Sets command frequency when selected.

0.1 Hz

62

[Preset Freq 1]

0xB3-1-62

Sets command frequency when selected.

0.1 Hz

63

[Preset Freq 2]

0xB3-1-63

Sets command frequency when selected.

0.1 Hz

64

[Preset Freq 3]

0xB3-1-64

Sets command frequency when selected.

0.1 Hz

65

[Preset Freq 4]

0xB3-1-65

Sets command frequency when selected.

0.1 Hz

66

[Preset Freq 5]

0xB3-1-66

Sets command frequency when selected.

0.1 Hz

67

[Preset Freq 6]

0xB3-1-67

Sets command frequency when selected.

0.1 Hz

68

[Preset Freq 7]

0xB3-1-68

Sets command frequency when selected.

0.1 Hz

69

[Accel Time 2]

0xB3-1-69

Sets second acceleration rate.

0.1 Seconds

70

[Decel Time 2]

0xB3-1-70

Sets second deceleration rate.

0.1 Seconds

71

[IR Compensation]

0xB3-1-71

Adds a voltage to the output based on the torque current.

1%

72

[Slip Comp]

0xB3-1-72

Compensates for the inherent slip of the motor.

0.1 Hz

73

[Reverse Disable]

0xB3-1-73

Setting to 1 disables the reverse.

Numeric Value

74

[Analog Select]

0xB3-1-74

Selects between unipolar and bipolar analog input.

Numeric Value

75

[Analog Minimum]

0xB3-1-75

Sets the percent of the analog input used to represent
P32 - [Minimum Frequency].

0.1%

76

[Analog Maximum]

0xB3-1-76

Sets the percent of the analog input used to represent
P33 - [Maximum Frequency].

0.1%

78

[Compensation]

0xB3-1-78

Some drive/motor combinations have inherent instabilities
which are exhibited as non-sinusoidal motor currents. A
setting of 1 will enable the compensation to correct this
condition. A setting of 0 disables this function.

Numeric Value

79

[Curent Trip]

0xB3-1-79

Percent above P43 - [Current Limit] at which the drive trips
immediately.

1%

This parameter applies only to the Analog Signal Follower model.

This parameter applies only to the Preset Speed model.

Advertising