Run mode, Error mode, Run mode -2 error mode -2 – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual

Page 28: Modes of operation (continued)

Advertising
background image

Publication 0160-5.18 - June 2003

4-2

Modes of Operation

Modes of Operation (Continued)

Power-up Reset Mode (Continued)

If the power up or reset sequence fails, the COMM LED will turn
solid red and the 160-DN2 module will enter the Error mode (see
heading below for more information).

Run Mode

After a successful power-up or reset, the 160-DN2 module enters the
run mode and operates as a slave device to a master device. In run
mode, the module:

• Accepts messages from the master on the DeviceNet network.

• Monitors DeviceNet incoming power.

If an error is detected, the 160-DN2 module will enter the Error mode
(see heading below for more information).

Error Mode

If the 160-DN2 module detects an error, the COMM LED is affected.
Errors are critical or noncritical, and are summarized below.

See

Chapter 7

,

Troubleshooting

for details in the troubleshooting

chart on how to recover from an error.

Table 4.A COMM LED State During Power-up Reset Mode

COMM LED State

Description

Flashes Green 1/4 second,

Red 1/4 second,

then goes blank

Occurs when power is applied to module.

Blank

Power-up initialization is taking place.

Solid Red

160-DN2 module is in Error mode. Indicates failed
initialization, duplicate node address or incorrect baud rate.

Solid Green

160-DN2 module is in the Run mode.

Table 4.B COMM LED State During Error Mode

COMM LED State

Error Type

Description

Solid Red

Critical

(not recoverable)

Power-up initialization failure.

Duplicate node address detected.

Incorrect baud rate.

Flashing Red

Non-Critical

(recoverable)

I/O connection timed out.

Off

Non-Critical

(recoverable)

DeviceNet power lost.