Publication 0160-5.18 - June 2003

Troubleshooting

7-5

Understanding the FAULT LED
(Continued)

Table 7.C DeviceNet Fault Codes (Class 0x29, Instance 1, Attribute 13) (Continued)

Fault Code

(hex)

Fault

Indication

Description

Corrective Action

2342

UW Short

Excessive current has been detected between these
two drive output terminals.

Check the motor and external wiring to the drive output
terminals for a shorted condition.

2343

VW Short

Excessive current has been detected between these
two drive output terminals.

Check the motor and external wiring to the drive output
terminals for a shorted condition.

3120

Power Loss

DC Bus voltage remains below 85% nominal on power
up for longer than 5 seconds.

Monitor incoming AC line for low voltage or line power
interruption.

3210

Over Voltage

DC Bus maximum voltage exceeded.

Bus overvoltage caused by motor regeneration. Extend
the decel time, or install dynamic brake option or external
capacitor module. Check for high line voltage.

3220

Under Voltage

DC Bus voltage fell below the minimum value while the
motor was running.

Monitor incoming AC line for low voltage or line power
interruption.

4310

Over Temperature

Excessive heat detected.

Clear blocked or dirty heat sink fins. Check ambient
temperature. Check for blocked or non-operating fan.

5300

Drive Reset

Stop input not present.

Check stop input at TB3 terminal 8.

6310

EEPROM Fault

EEPROM has invalid data.

Reset EEPROM.

6311

DeviceNet Module

EEPROM Fault

DevicNet 160-DN2 module EEPROM has invalid data.

Reset to factory defaults using P56 - [Reset Defaults].

7121

Motor Stalled

Motor has stalled. Motor load is excessive.

Longer accel time or reduced load required.

7122

Motor Overload

Internal electronic overload trip. Excessive motor load
exists.

Reduce motor load.

7421

Reprogramming

Fault

Occurs when drive parameters are reset to defaults.

Clear fault.

7500

No DeviceNet Power 24 volt network power is not detected.

Check DeviceNet connector at module. Also, check the
network’s power supply.

7501

DeviceNet Lost

I/O Connection

Polled I/O connection timed out.

Check DeviceNet Master for correct operation (i.e.,
powered up, scanner online, etc.).

7502

DeviceNet

Unrecoverable Fault

No communication is occurring. Fault occurs when
duplicate node address exists or wrong baud rate is set.

Check DIP switch settings for proper baud rate and node
address.

7503

DeviceNet Transmit

Fault

A transmit timeout occurred.

Power drive off, and then cycle power on.

7504

DN Forced Fault

DeviceNet module forced a fault.

Clear fault.