Understanding the fault led, Understanding the fault led -3 – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual

Page 77

Advertising
background image

Publication 0160-5.18 - June 2003

Troubleshooting

7-3

Understanding the FAULT LED

When the FAULT LED is Red, a drive fault is present. To view the
fault code, you must either view P7 - [Present Fault] or read the
value of Class 0x29 (Control Supervisor Object) Instance 1 Attribute
13 (Fault Code).

If you view P7 - [Present Fault], refer to

Table 7.B

for an

explanation of each fault code. If you read the value of Attribute 13
(Fault Code), refer to

Table 7.C

.

Table 7.B Bulletin 160 SSC Interface Fault Codes

Fault Code

Fault

Indication

Description

Corrective Action

0

No Fault

The drive is currently not faulted.

No action required.

3

Power Loss

DC Bus voltage remains below 85% nominal on power
up for longer than 5 seconds.

Monitor incoming AC line for low voltage or line power
interruption.

4

Under Voltage

DC Bus voltage fell below the minimum value while the
motor was running.

Monitor incoming AC line for low voltage or line power
interruption.

5

Over Voltage

DC Bus maximum voltage exceeded.

Bus overvoltage caused by motor regeneration. Extend
the decel time, or install dynamic brake option or external
capacitor module. Check for high line voltage.

6

Motor Stalled

Motor has stalled. Motor load is excessive.

Longer accel time or reduced load required.

7

Motor Overload

Internal electronic overload trip. Excessive motor load
exists.

Reduce motor load.

8

Over Temperature

Excessive heat detected.

Clear blocked or dirty heat sink fins. Check ambient
temperature. Check for blocked or non-operating fan.

11

Operator Fault

The keypad has been removed while the drive is
powered or there is excessive noise on the network.

Clear the fault. Do not remove the keypad under power.
Eliminate excessive noise on the network.

12

Over Current

Overcurrent detected in hardware trip circuit.

Check short circuit at the drive output or excessive load
conditions at the motor.

20

Drive Overload Fault An internal electronic overload trip has occurred. The

drive is over heating.

Clear blocked or dirty heat sink fins. Check ambient
temperature. Check for blocked or non-operating fan.
Reduce motor load current.

22

Drive Reset

Stop input not present.

Check stop input at TB3 terminal 8.

32

EEPROM Fault

EEPROM has invalid data.

Reset EEPROM using P56 - [Reset Functions].

33

Max Retries Fault

Drive did not reset fault within the max retries specified. Repair system fault.

36

Incompatible Fault

Incompatible communication module is installed.

Verify compatibility of communication module.

38

Phase U

Phase to ground fault detected between drive and motor
phase U.

Check wiring between drive and motor. Check motor for
grounded phase.

39

Phase V

Phase to ground fault detected between drive and motor
phase V.

Check wiring between drive and motor. Check motor for
grounded phase.

40

Phase W

Phase to ground fault detected between drive and motor
phase W.

Check wiring between drive and motor. Check motor for
grounded phase.

41

UV Short

Excessive current has been detected between these
two drive output terminals.

Check the motor and external wiring to the drive output
terminals for a shorted condition.

42

UW Short

Excessive current has been detected between these
two drive output terminals.

Check the motor and external wiring to the drive output
terminals for a shorted condition.

Advertising