Class code 0x29 - control supervisor object, B-13, Class code 0x29 — control supervisor object – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual

Page 95

Advertising
background image

Publication 0160-5.18 - June 2003

DeviceNet Information

B-13

Class Code 0x29 —
Control Supervisor Object

Instance 1 Attributes

Bulletin 160 specific instance attributes.

Setting Attribute ID 100 to “0” will cause the slave to expect no control information from the master. Likewise, setting Attribute ID 101 to “0” will cause
the master to expect no status information from the slave.

Class Attributes: None Supported

Number of Instances: 1

Attribute ID

Access

Rule

Name Data

Type

Min/Max

Default

Description

3

Get/Set

RunFwd

BOOL

0 to 1

0

See page

B-15

.

4

Get/Set

RunRev

BOOL

0 to 1

0

See page

B-15

.

5

Get/Set

NetCtrl

BOOL

0 to 1

0

See page

B-15

.

6

Get

State

USINT

0 to 7

3 = Ready
4 = Enabled
7 = Faulted
(See

Figure B.1

on page

B-14

.)

7

Get

RunningFwd

BOOL

0 to 1

0

1 = (Enabled and RunFwd)
0 = Other State

8

Get

RunningRev

BOOL

0 to 1

0

1 = (Enabled and RunRev)
0 = Other State

9

Get

Ready

BOOL

0 to 1

1 = Ready or Enabled
0 = Other State

10

Get

Faulted

BOOL

0 to 1

1 = Fault Latched
0 = No faults present

12

Get/Set

FaultRst

BOOL

0 to 1

0

0 -> 1 = Fault Reset
0 = No Action

13

Get

FaultCode

UINT

0 to 7504hex

0

In Faulted state, FaultCode indicates the fault that caused
the transition to Faulted. If not in Faulted state, FaultCode
indicates the fault that caused the last transition to the
Faulted state.
Fault codes are listed in Chapter 7,

Table 7.B

.

15

Get

CtrlFromNet

USINT

0 to 1

0

Status of Run/Stop control source.
0 = Control is Local
1 = Control is from the network

16

Get/Set

DNFaultMode

USINT

0 to 1

0

Mode that determines the drive’s behavior when a
communication fault such as loss of DeviceNet power occurs.
0 = Fault the drive and issue a stop command
1 = Ignore the communication fault

17

Get/Set

Force Fault/Trip

BOOL

0 to 1

0

0 to 1 transition forces fault.

100

➀➁

Get/Set

OutputAssembly USINT

0 to 103

20

Output Assembly instance that is currently active.

101

➀➁

Get/Set

InputAssembly

USINT

0 to 105

70

Input Assembly instance that is currently active.

102

Get/Set

DNPresetCmd

USINT

0 to 7

0

DeviceNet Preset command. (Preset Speed Units Only.)