Chapter 5
Inputs, Outputs and Switch Settings

5-3

Terminal Block - TB3 (A Quad B Board)

Figure 5.1 provides interconnect information between the position
controller and TB3 on the A Quad B Board.

ATTENTION: To guard against possible damage to the A
Quad B Board, assure that wiring between TB3 and the position
controller is correct. Refer to Figure 5.1.

!

Figure 5.1
A Quad B Board Wiring

Important: Note terminal orientation prior to wiring.

1

TB2

20

1

TB3

10

1

Recommended Wire – Belden #9728 or equivalent. Maximum distance between the A Quad B Board and
the position controller is 40 feet (12.2 meters) using a 5 volt signal. For distances up to 300 feet (91 meters),
18 AWG (0.8 mm

2

) wire (Belden 9388 or equivalent) and an 8 to 15V DC power supply must be used.

2

For proper operation when interconnecting to IMC classic products (IMC 110, 12x), the B and B (NOT)
signals must be reversed.

3

When interfacing to IMC 121 or 123 controllers, use the 1391-CAQB cable. When interfacing to the
integrated packages of the MAX or S Class controls, use the 1391-SAQB or 1391 SAQBK cable.

TB3
Number

1
2
3
4
5
6
7
8
9
10

Description

A
A (NOT)
B

2

B (NOT)

2

Z
Z (NOT)
+5V DC (

±

5%)

Signal Common
+8 to +15V DC In
No Connection

A Quad B Board

To Position

Controller

1

Power Supply

Input

1

9

8

7

6

5

4

3

2

1

2

1

S1

Top Logic Control Board

The A Quad B option operates in the same manner as the Allen-Bradley
845H Line Driver Encoder (26LS31 line driver output). The option
requires either a regulated +5V DC at terminal 7 or an unregulated +8 to
+15V DC input at terminal 9 (board draws 125mA maximum). The pulse
train output is selectable to 256, 512, 1024 or 2048 lines per revolution via
the Encoder Output switch, S1 (see page 5-6).

Terminal Block - TB4

Please note that there are no connections to TB4-20 & 22.

Contactor Coil (TB4, Terminals 11, 12)
Connections to the coil of the integral contactor are performed at these
terminals. The coil voltage is 115V AC, 50/60 Hz.

Important: Drives with a catalog number of 1391-DESxx-DI-AQB-A will
have a 24V DC coil. Drives with a catalog number of 1391-DESxx-DI-
AQB-B will have a 240V AC coil.