Chapter 6
Programming

6-18

Parameter 169 – Kl Velocity Loop (Intg Gain ki)

This parameter controls the integral error gain of the velocity regulator. For
example, if KI = 8, then velocity (1000 rpm) error for 1 second will
produce a (rated motor) current torque reference.

Parameter Type:

View/modify in Modify level and Maintenance level

Minimum Value:

0

Maximum Value:

24000

Default Value:

6667

Parameter 170 – Feed Forward Gain (Feed Frwd Gain)

Controls the feedforward gain of the velocity regulator. Setting this to a
value greater than zero reduces the velocity feedback overshoot in response
to a step change in the velocity reference. The velocity loop response to a
load disturbance is unaffected by the Feed Forward Gain.

Parameter Type:

View/modify in Modify level and Maintenance level

Minimum Value:

0

Maximum Value:

0.39

Default Value:

0

Parameter 171 – Static Gain/Droop

Specifies the velocity regulation tolerance in rpm.

Parameter Type:

View/modify in Modify level and Maintenance level

Minimum Value:

0 rpm

Maximum Value:

15.6 rpm

Default Value:

1 rpm

Parameter 172 – Velocity Loop Integrator Preset (Intg Prest Val)

The velocity loop integrator will be set to the value in this parameter when
the drive transitions into the run state.

Parameter Type:

View/modify in Maintenance level

Minimum Value:

–200% rated motor current

Maximum Value:

+200% rated motor current

Default Value:

0

Parameter 181 – Motor Inertia

Displays the time it will take for the selected motor to reach 1000 rpm at
100% of rated torque. This assumes that the motor has 0.2 times the motor
inertia connected to it, representing typical system inertia (couplings, etc.)

Parameter Type:

View/modify in Maintenance level

Minimum Value:

0 ms

Maximum Value:

500 ms

Default Value:

Set by “Setup drive with motor data” routine

Parameter 182 – Desired Velocity Bandwidth (Desired Vel BW)

This is associated with the Auto Tune Calculate function and allows the
user to enter a desired velocity bandwidth less than or equal to the
Maximum Bandwidth (parameter 68) as calculated by the auto tune cycle.

Parameter Type:

View/modify in Modify level and Maintenance level

Minimum Value:

1 rads/second

Maximum Value:

250 rads/second

Default Value:

200 rads/second – To convert rads/second to Hertz, divide by 6.28.