Shunt fusing – Rockwell Automation 1391 USER MNL/DIGITAL AC SERVO DR User Manual

Page 94

Advertising
background image

Chapter 10
Transformers and Shunt Regulators

10-6

ATTENTION: Proper derating must be applied to the
manufacturers nominal resistor power ratings when using these
in external shunt configurations. Consult the resistor
manufacturer for recommended derating. Failure to comply
could result in personal injury and/or equipment damage from
an overheated resistor.

!

Shunt Fusing

Shunt regulator fusing is provided with all of the 1391-DES drives. The
fuse is in series with the resistor and used to protect the resistor against
short circuits. The shunt fuse is located on top of the drive near the circuit
breaker for 15 and 22.5A drives. External resistors for 22.5A and 45A
drives are supplied with a fuse which must be mounted external to the
drive (see Appendix A for mounting dimensions). Refer to Table 10.C for
further shunt fuse information.

Table 10.C
Shunt Fuse Information

Drive Rating

15A

22.5A

22.5A

45A

Fuse Location

Top Panel

Top Panel

External

External

Fuse Type

Bussmann KLM-10 or equivalent

Bussmann FNM-6.25 or equivalent

Bussmann KTK-15 or equivalent

Bussmann KLM-20 or equivalent

Important: Repeated overvoltage tripping can be an indication that the
shunt fuse has malfunctioned.

Advertising