Fusing (transformer primary), External shunt regulator resistor, Interface connections – Rockwell Automation 1391 USER MNL/DIGITAL AC SERVO DR User Manual

Page 68

Advertising
background image

Chapter 7
Installation

7-7

Table 7.B
Minimum Transformer Wire Sizes – AWG (mm

2

)

Input Voltage

208V AC

240V AC

380V AC

415V AC

480V AC

575V AC

1.5

#12 (2.5)

#12 (2.5)

#12 (2.5)

#12 (2.5)

#12 (2.5)

#12 (2.5)

3.5

#12 (2.5)

#12 (2.5)

#12 (2.5)

#12 (2.5)

#12 (2.5)

#12 (2.5)

5.0

#12 (2.5)

#12 (2.5)

#12 (2.5)

#12 (2.5)

#12 (2.5)

#12 (2.5)

10.0

#8 (6)

#8 (6)

#10 (4)

#12 (2.5)

#12 (2.5)

#12 (2.5)

12.5

#8 (6)

#8 (6)

#10 (4)

#10 (4)

#10 (4)

#12 (2.5)

15.0

#6 (10)

#8 (6)

#8 (6)

#10 (4)

#10 (4)

#10 (4)

kVA

Important: The transformer primary requires protection by means of a
customer supplied branch circuit disconnect device. Refer to Appendix B.

Fusing (Transformer Primary)

Time delay fusing similar to Bussman Fusetron FRS Series or equivalent
must be used if the primary circuit is fused. Circuit breakers must provide
protection equivalent to fuses.

Fuse ratings shown in Table 7.C are the highest ratings allowed in a 25

°

C

(77

°

F) ambient temperature. Higher electrical enclosure ambient

temperatures will require fuses with higher current ratings. Consult fuse
manufacturer’s derating data. Fuses larger than those listed below may
result in transformer damage.

Table 7.C
Fuse Current Rating – Amperes

Primary Voltage

208V AC

240V AC

380V AC

415V AC

480V AC

575V AC

1.5

8

7

4.5

4

3.5

3

3.5

17.5

15

9

8

7

6

5.0

20

20

12

12

10

8

10.0

40

35

25

20

17.5

15

12.5

50

45

30

25

25

20

15.0

60

50

35

30

30

25

kVA

External Shunt Regulator Resistor

The external Shunt Regulator Resistor and fuse for the 45A 1391-DES
must be connected to TB5-8 and TB5-9 as described in Chapter 10.

22.5A drives must be converted for use with an external shunt resistor and
fuse. Refer to Chapter 10 and Appendix B for detailed instructions.

Interface Connections

Refer to Chapter 5 and Appendix B for connection information.